Ex118BSSRF RANGE – 11,000 volts, 800 amp, removable flange, flame proof coupler

At AusProof we strive to innovate and our Ex118BSSRF range is no exception.

This design removes the guesswork out of having to make crucial decisions on whether or not the flameproof path is under discretion to be put back in service, or removed for replacement.

The cost involved in this is unmeasurable. With our Ex118BSSRF range, this decision has now become easier. The process has been limited so that the only requirement is the removal of 4 simple screws and the front flange can be replaced in any environment without having to move the cable. This operation can be done by anyone at anytime with no prerequisite skillset. This is the perfect design for the customer looking to save time and money.

Contact us

  • Features

    • Removable Flange
    • Live Line indicators
    • IP68 rating
    • Pilots protection
    • Solid face and body Casting
    • Higher Mpa Stainless steel Material
    • More resistant to damage on flameproof paths
    • Tensions the gland without removing the clamp
    • Detachable Adaptor Flange
    • Handles
    • All air expelled on joining
    • Silicon seal for face
    • Full phase to earth segregation
    • Arc extinguishing Phase Insulators
    • Genderless design
    • Silicon Phase Connectors
  • Accessories

    • Adaptor – Gear Mount
    • Cast Protection Cover
    • Contacts Crimp
    • Contacts Soldered
    • Gland – Armoured
    • Gland – Unarmoured
    • Insulated End Cover
    • Slide Hammer
    • Coupling Tool

Technical Information

  • Specs

    Volts 11,000
    Amp 800
    LOA (mm) 740
    Weight (KG) 22
    Material Stainless steel
    Volume (Litres) 4.0

    Download Product Dimensions

  • Test Results

    Manufactured to AS/NZS 1300:2009
    AS/NZS 60079.0:2008
    AS/NZS 60079.0:2008
    Through Fault Current at 10 minute intervals 20kA for 0.3 seconds
    20kA for 0.3 seconds
    20kA for 1.0 seconds
    AC HV Withstand 24kV for 1 minute
    50kV for 1 minute
    35kV for 6 hours
    Impulse Voltage 95kV
    110kV
    Partial Discharge 10pC Prior to 6 hour HV withstand
    0.6pC After 6 hour HV withstand
    Temperature Rise 800A